Herco UO-D 600 FU 600 lph Reverse Osmosis System 387 161

SKU: 18231000205 | 5110010184
Regular price £13,764.54
Shipping calculated at checkout.

Technical Resources

Questions & Answers loading...

Product Description

The reverse osmosis unit is used for the desalination of softened water with a salinity of up to 1,000 mg/l. It is equipped with a high-quality centrifugal pump with variable-speed drive (VSD = FU). Frequency-controlled operation reduces electricity cost by 30 - 50 %, extends the lifespan of the unit and keeps permeate production constant irrespective of operation pressure. The RO digital microprocessor controller enables fully automatic operation with logging of all relevant operating data and freely adjustable limit values. The unit can be connected to the central control system via an optional Profinet interface.

Benefits

• Compact unit
• Equipment with VSD (FU) saves 30 - 50 % electricity cost, maintains permeate production constant and enables a longer lifespan as well as particularly quiet operation
• Versatile RO digital controller with logging of operation data and many parametrization options

Applications

• Desalination of softened water
• Suitable for all commercial and industrial applications
• Suitable for reduction of electricity cost

Controller : RO digital
Desalination rate min.: 97 %
Permeate recovery: 75 – 80 %
Permeate back pressure max.: 0.3 bar
pH value operation: 3.6 – 9.5
pH value cleaning: 2 – 12
Ambient temperature: 5 – 40 °C

Conditions of use: The unit may only be used for the desalination of softened feed water with drinking water quality or appropriately pre-treated well or surface water. The unit is designed for a salinity (TDS) of 1,000 mg/l and a temperature of 15 °C. Under these conditions, the projected permeate output is achieved even after three years of operation. The permeate yield depends on the raw water quality and the pre-treatment. The following parameters must be maintained in the feed water:

Free chlorine: not detectable
Iron (Fe): < 0.2 mg/l
Manganese (Mn): < 0.05 mg/l
Silica (SiO2): < 25 mg/l
Silt density index (SDI): < 3
Feed water temperature: 5 – 35 °C
Feed water pressure: 2 – 6 bar
Pressure fluctuation: ± 0.5 bar

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Maestro
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

Frequently Asked Questions

What makes the Herco UO-D 600 FU 600 lph reverse osmosis system energy-efficient?
The Herco UO-D 600 FU 600 lph features a high-quality centrifugal pump with a variable-speed drive (VSD), which reduces electricity costs by 30-50%, maintains consistent permeate production, and extends the unit's lifespan.
Is the Herco UO-D 600 FU suitable for industrial use?
Yes, the Herco UO-D 600 FU is designed for all commercial and industrial applications, capable of desalinating softened water with a salinity of up to 1,000 mg/l, making it versatile for various industrial needs.
How does the digital controller enhance the operation of the reverse osmosis system?
The RO digital microprocessor controller enables fully automatic operation, logs all relevant operating data, and offers many parameters for customization, ensuring efficient and reliable system performance.
What water quality parameters are necessary for optimal operation of the Herco UO-D 600 FU?
For optimal operation, the feed water should have no detectable free chlorine, iron less than 0.2 mg/l, manganese under 0.05 mg/l, silica below 25 mg/l, and a silt density index of less than 3, with a temperature of 5–35°C and pressure of 2–6 bar.
Can the Herco UO-D 600 FU be integrated with a central control system?
Yes, the unit can be connected to a central control system via an optional Profinet interface, allowing for integrated management and monitoring of the system.