Product Description
The permeate-staged reverse osmosis is used for the desalination of softened water with a salinity of up to 1,000 mg/l and is equipped with a compact rotary vane pump. Due to the double-stage design, a permeate conductivity of approx. 5 µS/cm is typically reached. The RO digital microprocessor controller (one controller per stage) enables fully automatic operation with logging of all relevant operating data and freely adjustable limit values. The unit can be connected to the central control system via an optional Profinet interface.
Benefits
Very good permeate quality is achieved through two-stage design
Subsequent upgrade from standard to permeate-staged unit easy to carry out
Flexible installation in confined spaces, stages can even be spatially separated if required
Applications
Desalination of softened water
Ideal for applications with strict requirements on permeate conductivity (e.g. in surface technology, chemical industry, laboratory technology etc.)
Controller :RO digital
Desalination rate min.:99.5 %
Permeate recovery stage 1:75 - 80 %
Permeate recovery stage 2:85 %
Permeate back pressure max.:0.3 bar
pH value operation:3.6 9.5
pH value cleaning:2 12
Ambient temperature:5 40 °C
Conditions of use: The unit may only be used for the desalination of softened feed water with drinking water quality or appropriately pre-treated well or surface water. The unit is designed for a salinity (TDS) of 1,000 mg/l and a temperature of 15 °C. Under these conditions, the projected permeate output is achieved even after three years of operation. The permeate yield depends on the raw water quality and the pre-treatment. The following parameters must be maintained in the feed water:
Free chlorine:not detectable
Iron (Fe):< 0.2 mg/l
Manganese (Mn):< 0.05 mg/l
Silica (SiO2):< 25 mg/l
Silt density index (SDI):< 3
Feed water temperature:5 35 °C
Feed water pressure:2 6 bar
Pressure fluctuation:± 0.5 bar